Documentation of the PLC software

<< Click to Display Table of Contents >>

Navigation:  General Implementation Instructions > Technical documentation >

Documentation of the PLC software

 

SPS programs must be handed over to the client on a data carrier or a designated storage location. The list format is A4 portrait. The software version must correspond to the version at the time of acceptance. Changes made by the manufacturer after acceptance must also be updated immediately on the data carrier or in a designated storage location.

The documentation of the control system must include the following lists in the following order:

 

Module list or object list

Variable list

Assignment plan inputs, outputs

Parameter list and default values

XML files

 

 

The storage location must contain all original data and source codes generated during the creation of the program, translated executable programs, as well as a memory dump of the AN with the latest valid version.